Fixes #3126: Incorrect calculation of PowerFeed available power
This commit is contained in:
@@ -1973,7 +1973,7 @@ class PowerPort(CableTermination, ComponentModel):
|
||||
)
|
||||
utilization['name'] = 'Leg {}'.format(leg_name)
|
||||
utilization['outlets'] = len(outlet_ids)
|
||||
utilization['available_power'] = powerfeed_available / 3
|
||||
utilization['available_power'] = round(powerfeed_available / 3)
|
||||
stats.append(utilization)
|
||||
|
||||
return stats
|
||||
@@ -2998,7 +2998,7 @@ class PowerFeed(ChangeLoggedModel, CableTermination, CustomFieldModel):
|
||||
|
||||
@property
|
||||
def available_power(self):
|
||||
kva = self.voltage * self.amperage * self.power_factor
|
||||
kva = self.voltage * self.amperage * (self.power_factor / 100)
|
||||
if self.phase == POWERFEED_PHASE_3PHASE:
|
||||
return kva * 1.732
|
||||
return kva
|
||||
return round(kva * 1.732)
|
||||
return round(kva)
|
||||
|
||||